Concrete Footing Depth: Frost Line, Soil Type & Building Codes

Footing depth is set by two rules: get below the frost line, and get onto soil that can carry the load. Here is how the codes set each, with real numbers and worked examples.

Updated 6 min read 6 sources cited
Excavated footing trench with a tape measure showing depth below grade
The short answer

Under the International Residential Code, exterior footings must sit on undisturbed soil at least 12 inches below grade and below the frost line your local building department sets in its climate table. That frost depth ranges from a few inches in the South to 42 inches in southern Minnesota and 60 inches in the north of the state. In England and Wales, strip foundations go at least 450 mm down for frost and about 1 m on high-shrinkage clay. Whichever requirement is deeper governs, and the width comes from the soil's bearing value.

12 inIRC minimum below undisturbed ground, everywhere
42–60 inMinnesota frost depth, south to north
1,500 psfpresumptive bearing for clay and silt (IRC)
On this page
  1. The two things that set footing depth
  2. How the codes handle frost
  3. Soil bearing and footing width
  4. Working out the concrete for the footing
  5. Common footing depth mistakes
  6. The bottom line

Your building department has the final number. Frost depth is set locally and printed in the jurisdiction's climate table. Check it, and any amendments, before digging. Structural footings for unusual loads or soils need an engineer.

The two things that set footing depth

A footing has to satisfy two separate depth requirements, and the deeper one governs:

  1. 1

    Below the frost line

    Soil that freezes can heave. The bottom of the footing must sit below the depth to which the ground freezes in your area, or the foundation must be protected from frost another way.

  2. 2

    On good bearing soil

    The footing must rest on undisturbed natural soil, below topsoil, organic material and loose fill, that can carry the load without settling. Under the IRC that is never less than 12 inches below the ground surface.

In cold climates the frost line usually governs. In warm climates the bearing requirement and the 12-inch minimum govern, and on expansive clay the depth needed to get below seasonal moisture change can govern instead.

How the codes handle frost

The IRC does not print one national frost depth. Each jurisdiction enters its frost line depth in Table R301.2(1), and section R403.1.4.1 says foundations must be protected from frost by one of four methods:

MethodWhat it means
Extend below the frost lineThe usual approach: dig to the local frost depth
Frost-protected shallow foundation (R403.3)Rigid insulation keeps the ground under a heated building from freezing, so footings can be shallow
Design to ASCE 32The engineering standard behind frost-protected shallow foundations
Bear on solid rockRock does not heave

The model code also says footings must never bear on frozen soil unless it is permanently frozen.

Real frost depths: Minnesota as an example

Minnesota writes its frost depths into state rule, by county:

ZoneMinimum footing depthExample counties
Zone I (north)60 in (5 ft)St. Louis (Duluth), Clay (Moorhead), Beltrami, Itasca, Otter Tail
Zone II (south)42 in (3 ft 6 in)Hennepin and Ramsey (Twin Cities), Dakota, Olmsted (Rochester), Stearns

The rule allows less depth only with supporting evidence from an engineer competent in soil mechanics. Other cold states and cities set their own values; mild-climate jurisdictions may list only a few inches, in which case the 12-inch minimum takes over.

Exceptions in the model code

StructureFrost protection required?
Freestanding accessory building, light-frame, ≤ 600 sq ft, eave ≤ 10 ftNo (still 12 in minimum)
Freestanding accessory building, other construction, ≤ 400 sq ft, eave ≤ 10 ftNo
Deck not supported by the dwellingNo, in the model text
Deck attached to the houseYes
House, attached garage, porch footingsYes

Many jurisdictions amend these exceptions, so treat the table as the starting point. Minnesota, for instance, additionally allows slab-on-grade foundations for detached one-storey garages, carports and sheds up to 3,000 sq ft.

Frost in the UK

In England and Wales, strip foundations are taken to at least 450 mm below ground for frost, unless bearing on rock, and to about 1 m on high-shrinkage clay, where seasonal shrinking and swelling is the bigger risk. Near trees on clay, deeper foundations are needed and are set by the NHBC and the building control body.

Soil bearing and footing width

Once the depth is set, the footing must be wide enough that the soil is not overstressed. Without a soils report, the IRC allows these presumptive values:

Soil (IRC Table R401.4.1)Presumptive bearing
Crystalline bedrock12,000 psf
Sandy gravel and gravel (GW, GP)3,000 psf
Sand, silty sand, clayey sand, silty and clayey gravel (SW, SP, SM, SC, GM, GC)2,000 psf
Clay, sandy clay, silty clay, clayey silt, silt, sandy silt (CL, ML, MH, CH)1,500 psf

If the building official suspects soil weaker than 1,500 psf, a soils investigation is required. Peat, organic soil and uncompacted fill are never acceptable bearing.

Footing width and pad sizeStrip footing width = wall load per foot ÷ allowable bearing
3,000 lb/ft ÷ 1,500 psf = 2.0 ft (24 in)
Column pad area = column load ÷ allowable bearing
30,000 lb ÷ 1,500 psf = 20 ft² → 4 ft 6 in × 4 ft 6 in (20.25 ft²)

For ordinary houses the IRC tabulates minimum widths directly:

Construction (IRC Table R403.1)1,500 psf2,000 psf3,000 psf≥ 4,000 psf
Light frame, 1 storey12 in12 in12 in12 in
Light frame, 2 storey15 in12 in12 in12 in
Light frame, 3 storey23 in17 in12 in12 in
Brick veneer or 8 in hollow block, 1 storey12 in12 in12 in12 in
Brick veneer or 8 in hollow block, 2 storey21 in16 in12 in12 in
8 in solid or grouted masonry, 2 storey29 in21 in14 in12 in

Spread footings must be at least 6 inches thick, with a projection beyond the wall of at least 2 inches and not more than the footing thickness. Check the edition your jurisdiction has adopted; table values have changed between editions.

Soil that heaves

Frost heave needs three things: freezing temperatures, a frost-susceptible soil and water. Silts and fine silty sands are the worst, because they draw water up to the freezing zone and grow ice lenses. Clean gravel and coarse sand drain freely and heave little. Good drainage around the footing, and keeping roof water away from the foundation, reduces the risk on any soil.

Working out the concrete for the footing

Strip footing

100 ft perimeter, 20 in wide × 8 in thick.

100 × 1.667 × 0.667 = 111 ft³ ÷ 27

≈ 4.1 yd³ (+5–10% waste)

Column pad

4 ft 6 in × 4 ft 6 in × 12 in thick.

4.5 × 4.5 × 1.0 = 20.25 ft³ ÷ 27

0.75 yd³ per pad

Deck pier, 10 in tube

42 in deep: π × (5 ÷ 12)² × 3.5 = 1.91 ft³

≈ 0.07 yd³ per post, about 3.2 bags of 80 lb mix (0.60 ft³ each)

The Concrete Footing Calculator does strip and pad footings; the Sonotube Calculator and Post Hole Calculator handle round piers.

Common footing depth mistakes

  • Using a national map instead of the local number. Frost depth is a local code value and may be deeper than any average map shows.
  • Measuring from finished grade that is not there yet. Depth is measured from the final ground surface. Lowering the grade later, for a patio or driveway, can leave footings too shallow.
  • Bearing on fill or topsoil. The bottom must be undisturbed natural soil; over-dug trenches are filled with concrete, not loose soil.
  • Shallow deck and porch footings. Attached decks and porches need the same frost depth as the house in most jurisdictions.
  • Pouring on frozen ground. Footings may not bear on frozen soil; protect the trench and the fresh concrete from freezing in winter.
  • Undersizing column pads. A 12 in wide footing under a 30,000 lb column on clay would load the soil far beyond 1,500 psf. Size the area from the load.

The bottom line

Get the frost depth from your building department, go at least that deep and never less than 12 inches below undisturbed ground, and size the width from the soil's bearing value. In the UK plan on at least 450 mm, and about 1 m on shrinkable clay. Look up your depth with the Frost Depth / Footing Depth Calculator, then size and price the concrete with the Concrete Footing Calculator.

Frequently asked questions

How deep should concrete footings be?

At least 12 inches below undisturbed ground and below your area's frost line, whichever is deeper. The frost depth comes from your local building department; in southern Minnesota, for example, it is 42 inches and in the northern counties 60 inches. In frost-free areas the 12-inch minimum still applies, and the footing must reach firm, undisturbed soil.

What happens if footings are not deep enough?

When soil under a footing freezes, water in it turns to ice lenses that lift the footing, and it drops back unevenly when it thaws. That frost heave cracks foundation walls, masonry and slabs and racks door and window frames. Repair usually means underpinning or rebuilding the affected footing.

Do deck footings have to go below the frost line?

Usually yes when the deck is attached to the house, because a heaving footing drags on the house ledger. The model IRC text has an exception for decks that are not supported by the dwelling, but many states and cities amend it, so check your local code before digging.

Does a shed or detached garage need frost-depth footings?

The IRC exempts freestanding accessory structures of light-frame construction up to 600 sq ft with eaves no higher than 10 ft (400 sq ft for other construction) from frost protection, though footings still need the 12-inch minimum. Minnesota, for example, also allows slabs on grade for detached one-storey garages, carports and sheds up to 3,000 sq ft. Local amendments vary.

How wide should a concrete footing be?

Wide enough that the load divided by the footing area stays within what the soil can carry. A wall bringing 3,000 lb per foot onto clay rated at 1,500 psf needs 3,000 ÷ 1,500 = 2 ft (24 in) of width. For ordinary houses the IRC tabulates minimum widths by storeys, wall type and soil: 12 in for a one-storey light-frame house on any listed soil, rising to 15 in for two storeys on 1,500 psf soil.

Can a footing be shallower with insulation?

Yes, for heated buildings designed as frost-protected shallow foundations under IRC section R403.3, which uses horizontal and vertical rigid insulation to keep the ground under the footing from freezing. The insulation sizes depend on your climate and must follow the code tables or ASCE 32.

Sources, author and reviewer

Depth rules and exceptions are quoted from the IRC text and state rules below; bearing values and widths from the IRC tables reproduced by building departments; UK depths from the Designing Buildings reference. Width and volume examples are calculated in the text.

  1. Minnesota Rules 1303.1600, Footing depth for frost protection. 60 in in Zone I and 42 in in Zone II counties; engineer may justify less; slab-on-grade allowance for small detached buildings
  2. IRC R403.1.4.1 Frost protection and exceptions (quoted on The Building Code Forum). four frost-protection methods, accessory-structure and deck exceptions, no bearing on frozen soil
  3. Humboldt County, NV, Residential foundation requirements. exterior footings at least 12 in below undisturbed ground (IRC R403.1.4)
  4. Garfield County, WA, Foundation requirements brochure. IRC Table R401.4.1 presumptive bearing values and Table R403.1 minimum footing widths
  5. City of Bloomington, MN, Foundation requirements handout. spread footings at least 6 in thick, projections at least 2 in, column footings sized for tributary load
  6. Designing Buildings Wiki, Strip foundation. UK strip foundations at least 450 mm deep for frost and at least 1 m on high-shrinkage clay
Rachel Sousa
Technical Writer & Content Lead · B.S. Civil Engineering, Purdue

Rachel holds a B.S. in Civil Engineering from Purdue University and spent 10+ years turning construction and engineering standards into clear documentation, including as documentation lead at a national ready-mix supplier. She writes every guide and calculator page on AllConcreteCalculator.com and owns the site’s editorial standards.

Published · Last updated · @rachelsousa101

Daniel Merritt, P.E.
Lead Structural Engineer · Licensed P.E., Civil/Structural · M.S. Structural Engineering, Texas A&M

Daniel is a licensed Professional Engineer with 18 years in concrete design and construction, from cast-in-place foundations and post-tensioned slabs to municipal bridge projects. He checks the engineering on this guide: that each code figure matches the provision it cites, the assumptions are stated, and the limits of the guidance are clear.

Technical review · @DanielMerrittco