🧪 Mix & Materials

Air Entrainment in Concrete: When and Where You Actually Need It

Entrained air is what lets outdoor concrete survive freeze-thaw cycles and de-icing salt. Here is when to specify it, how much, how to test it and where it does harm.

Updated 10 min read 7 sources cited
Air content pressure meter on a bucket of fresh concrete at a jobsite
The short answer

Specify air-entrained concrete for anything that will freeze while wet: driveways, walks, patios, steps, pool decks, exposed walls and footings above frost line in cold climates. Under ACI 318, the target total air for a typical 3/4 in stone mix is 5% for moderate exposure and 6% where the concrete stays wet or sees de-icing salt, with a ±1.5% tolerance. Do not use entrained air in interior floors that get a hard steel-trowel finish; it causes blisters and delamination.

5–6%target air, 3/4 in aggregate, moderate to severe exposure
±1.5%usual acceptance tolerance on the target
≈5%strength loss per 1% extra air
On this page
  1. Why freezing destroys non-air-entrained concrete
  2. Target air content by aggregate size and exposure
  3. Where to use it, and where not to
  4. How air is added: the admixture and the dose
  5. Checking the air at the truck
  6. Common mistakes
  7. The bottom line

Why freezing destroys non-air-entrained concrete

Hardened concrete is full of tiny capillary pores. When it is wet, those pores hold water, and water expands about 9% by volume when it freezes. In a dense paste there is nowhere for that expansion or the water it pushes ahead of it to go, so pressure builds until the paste cracks. Each freeze-thaw cycle opens the cracks a little further. On flatwork the result is scaling: the top layer of paste flakes off, exposing the stone, usually within a few winters. De-icing salt makes it much worse because it keeps the surface wetter and adds its own stresses.

Entrained air is a system of billions of microscopic, evenly spaced bubbles created by an air-entraining admixture added at the plant. The bubbles act as empty expansion rooms close to every part of the paste. For them to work, no point in the paste can be too far from a bubble: ACI 201 recommends a spacing factor of no more than 0.008 in (0.2 mm). That is why the total percentage alone is not the whole story, and why entrained air is different from the large, irregular "entrapped" voids left by poor consolidation, which do nothing for durability.

Entrained air, entrapped air and foamed concrete

Entrained airEntrapped airFoamed (cellular) concrete
How it gets thereAir-entraining admixture (ASTM C260)Mixing and incomplete consolidationPreformed foam blended into a cement slurry
Bubble sizeAbout 0.0004–0.04 in (10 µm–1 mm), round, evenly spaced0.04 in (1 mm) and larger, irregularLarge, closely packed cells
Amount4–7.5% total air in most exterior mixesAbout 3% with 3/8 in stone down to 1% with 1-1/2 in stone20% and far higher
PurposeFreeze-thaw and de-icer scaling resistanceNone; vibration removes most of itLow density for fill and insulation, not structural flatwork

Non-air-entrained concrete is not air-free: it still carries its 1–3% of entrapped air. The air meter reads total air, entrained plus entrapped.

Target air content by aggregate size and exposure

ACI 318 groups freeze-thaw exposure into classes. F0: concrete that does not freeze while wet. F1: freezes with only limited exposure to water. F2: freezes while frequently exposed to water. F3: freezes while frequently wet and exposed to de-icing chemicals. Smaller stone means more paste in the mix, so it needs more air.

Nominal maximum aggregate sizeMild (ACI 211.1)Moderate, F1Severe, F2 and F3
3/8 in (9.5 mm)4.5%6.0%7.5%
1/2 in (12.5 mm)4.0%5.5%7.0%
3/4 in (19 mm)3.5%5.0%6.0%
1 in (25 mm)3.0%4.5%6.0%
1-1/2 in (37.5 mm)2.5%4.5%5.5%
2 in (50 mm)2.0%4.0%5.0%
3 in (75 mm)1.5%3.5%4.5%

These are targets for total air, and a tolerance of ±1.5% is commonly applied at acceptance. A 3/4 in mix for a salted driveway therefore aims at 6% and is accepted between 4.5% and 7.5%.

The rest of the freeze-thaw recipe

Air alone does not make durable concrete. ACI 318 also limits the water-cement ratio and sets a minimum strength for each class:

ClassTypical exampleMax w/cmMin f′c
F0Interior slab, footing below frostNo limit2,500 psi
F1Vertical wall that sheds water0.553,500 psi
F2Exposed slab or step that stays wet, no salt0.454,500 psi
F3Driveway, walk or parking slab with de-icing salt0.405,000 psi

For F3 concrete ACI 318 also caps supplementary materials as a share of total binder: fly ash 25%, slag 50%, silica fume 10%. In the UK and Europe the equivalent classes are XF1–XF4 under EN 206, where Eurocode 2 lists at least 4% air for the XF2–XF4 classes.

What the air costs in strength

At the same water-cement ratio, each 1% of air takes about 5% off compressive strength. For a mix designed to reach 4,000 psi at its target air:

Air above targetApproximate strengthLoss
On target4,000 psiNone
+1%3,800 psi5%
+2%3,600 psi10%
+3%3,400 psi15%

Plants allow for this when they proportion an air-entrained mix: the bubbles make the concrete more workable, so the mix needs less water and the water-cement ratio is lowered to win the strength back. That is why an air-entrained 4,000 psi mix is routine, and why the damage comes from air that is over the target, not from air that was designed in.

Canada and the UK

CodeAggregate sizeRequired air
Canada, CSA A23.1, category 1 (classes C-1, C-2, F-1)10 mm6–9%
14–20 mm5–8%
28–40 mm4–7%
Canada, CSA A23.1, category 2 (classes C-4, F-2)10 mm5–8%
14–20 mm4–7%
28–40 mm3–6%
UK, BS 8500, freeze-thaw classes with entrained air10 mmAt least 5.5%
14 mmAt least 4.5%
20 mmAt least 3.5%
40 mmAt least 3.0%

Canadian ranges are acceptance limits, so a 20 mm driveway mix is ordered at 5–8%, a little higher than the US 6% ±1.5%.

Where to use it, and where not to

Use air-entrained concreteDo not use it
Driveways, aprons, walks, patios and pool decks in freezing climatesInterior floors that get a hard steel-trowel or burnished finish
Steps, stoops, curbs and guttersBasement and heated-building slabs that never freeze
Exposed walls, piers and foundation tops that get wetFootings and walls below the frost line
Parking slabs and anything that sees de-icing saltWarm climates where concrete never freezes wet

The trowel rule comes from ACI 302.1R and ACI 301: on a dense, hard-troweled interior surface, entrained air raises the risk of blisters and delamination because the trowel seals the surface while air and bleed water are still rising. Exterior flatwork is given a broom or float finish for this reason.

Air entrainment also makes fresh concrete more cohesive and workable and reduces bleeding, which is why some low-slump paving mixes use a little even where freezing is not a concern.

Air or no air, by project

ProjectClimate that freezesClimate that never freezes
Driveway, apron, parking slabYes: 6% with 3/4 in stone, w/cm 0.45, or 0.40 with saltNo
Sidewalk, patio, pool deckYes: 6%No
Steps, stoops, curbsYes: 6%No
Garage floorYes: 5–7%, light trowel or fine broom finish; see garage floorsNo
Foundation, basement or exterior wall exposed to weatherYes: about 5% (F1)No
Retaining wall stemYes: 5–6%, it stays damp on the soil sideNo
Footing below the frost line, including under a retaining wallNoNo
Deck pier or post footingYes for the part at and above gradeNo
Interior or basement slab in a heated buildingNoNo
Hard-troweled or burnished floor, any locationNo: keep total air at 3% or lessNo

Air or no air, by US climate

The residential code (IRC) decides it with a weathering map: concrete exposed to weather in the moderate and severe regions must be air-entrained with 5–7% total air; in the negligible region it need not be.

Weathering regionWhere, roughlyEntrained air for exposed concrete
SevereThe northern states and mountain West: Michigan, Ohio, New York, Minnesota, Colorado, northern Nevada including RenoRequired
ModerateA band across the mid-South and Pacific Northwest: Tennessee, North Carolina, Arkansas, western Oregon and WashingtonRequired
NegligibleFlorida, the Gulf Coast including Houston and southern Louisiana, southern Arizona including Phoenix, coastal southern California, HawaiiNot required

State lines do not follow the map. Phoenix needs no air; Flagstaff, at 7,000 ft in the same state, does. Your building department's climate table gives the region for your address.

IRC minimum 28-day strength by element (Table R402.2):

ConcreteNegligibleModerateSevere
Basement walls, foundations and other concrete not exposed to weather2,500 psi2,500 psi2,500 psi
Basement slabs and interior slabs on grade, except garage floors2,500 psi2,500 psi2,500 psi
Basement, foundation and exterior walls and other vertical concrete exposed to weather2,500 psi3,000 psi, air-entrained3,000 psi, air-entrained
Porches, carport slabs and steps exposed to weather, and garage floor slabs2,500 psi3,000 psi, air-entrained3,500 psi, air-entrained

For a steel-troweled garage floor the IRC allows the air to drop to 3% if the strength is raised to 4,000 psi. These are code minimums for houses; ACI 318 class F2 and F3 mixes in the tables above are stronger and are the better order for a salted driveway.

How air is added: the admixture and the dose

Air is entrained with a liquid air-entraining admixture meeting ASTM C260: a surfactant based on wood resin, tall oil or synthetic detergents that stabilises the bubbles the mixer folds in. The plant dispenses it with the mix water. It is not difficult for a ready-mix plant, which does it on every exterior load in cold regions; it is difficult to control in a site mixer, because the result has to be measured.

Admixture doseDose (fl oz) = cement (lb) ÷ 100 × rate (fl oz per 100 lb)
Typical rate: 1/4 to 4 fl oz per 100 lb of cement and other binder (16–260 mL per 100 kg)
8 yd³ truck, 564 lb/yd³ mix, 1 fl oz rate: 8 × 564 ÷ 100 × 1 = 45 fl oz (1.3 L)
10 ft³ site batch of the same mix: 10 ÷ 27 × 564 ÷ 100 × 1 = 2.1 fl oz (62 mL)

One fluid ounce per 100 lb is 65 mL per 100 kg, so a 335 kg/m³ mix at that rate takes about 220 mL per cubic metre. There is no standard dose: the rate is a starting point for a trial batch, then the air meter decides. The same dose gives different air when conditions change:

ChangeEffect on air at the same dose
Hotter concreteLess air; dose goes up in summer
Higher slump, up to about 6 inMore air
More fines in the sand, finer cement, more cementLess air
Fly ash, especially with high carbon contentLess air, sometimes much less
Water reducer in the mixMore air; the air-entrainer dose is cut
Long haul or extended mixingAir is gradually lost
Pumping and heavy vibrationAir is lost

Cost is small. Air-entrained mixes usually add a few dollars per cubic yard, and many plants in freezing regions supply exterior mixes with air as standard. The Admixture Dosage Calculator converts a rate into ounces or millilitres for your load.

Checking the air at the truck

  1. 1

    Order it properly

    Give the plant the exposure class or the target air content with tolerance (for example, "6% ±1.5%"), the maximum water-cement ratio and the strength. "Air-entrained" on its own is not a specification.

  2. 2

    Sample the middle of the load

    Take the test sample from the middle portion of the truck, not the first concrete out of the chute.

  3. 3

    Test it

    Use a pressure meter (ASTM C231) for normal stone, or a volumetric roll-a-meter (ASTM C173) for lightweight or porous aggregate. Both read total air in a few minutes.

  4. 4

    Act on the result

    Out of tolerance? Do not place it until the plant adjusts the dose. Air can also be lost by long hauls, pumping and over-vibration, so retest if conditions change.

Common mistakes

  • Hard-troweling air-entrained exterior concrete. Use a float and broom finish outside. Steel-troweling seals the surface and invites blistering and scaling.
  • Air-entraining a power-troweled interior floor. No freeze-thaw benefit indoors, a real risk of delamination.
  • Adding water at the truck. Retempering raises the water-cement ratio above the F2/F3 limits and lowers strength, undoing much of what the air was meant to protect.
  • Assuming more air is better. Each 1% over target costs about 5% of strength. Aim for the middle of the range.
  • Not testing. Without a test you do not know whether you placed 3% or 9%.
  • Salting a new slab. Even good air-entrained concrete should not see de-icing salt in its first winter; sweep or use sand instead.

The bottom line

If outdoor concrete can freeze while wet, order it air-entrained: about 5% total air for moderate exposure and 6% for wet or salted slabs with 3/4 in stone, more with smaller stone, plus a water-cement ratio of 0.45 or 0.40. Leave entrained air out of hard-troweled interior floors. Use the Air Entrainment Calculator to set the target and dose, and check the mix with the Water-Cement Ratio Calculator.

Frequently asked questions

Does all concrete in cold climates need air entrainment?

No, only concrete that can freeze while it is wet or saturated. Exterior flatwork, steps, exposed walls and anything that sees de-icing salt need it. Interior slabs, basement floors and footings below the frost line that stay above freezing do not, and interior floors with a hard-troweled finish should not have it.

How much air should concrete have for a driveway?

For a driveway in a freezing climate that sees snow, standing water or de-icing salt, ACI 318 treats it as severe exposure (class F2 or F3). With the usual 3/4 in stone the target is 6% total air, accepted from 4.5% to 7.5%. With 3/8 in pea-gravel mixes it is 7.5%. Order it with a maximum water-cement ratio of 0.45, or 0.40 if salt is used.

What happens if the air content is too high?

Strength drops. As a rule of thumb, each 1% of air above the target costs about 5% of compressive strength, so a mix that comes in 3% high can be some 15% weaker than designed. Very high air can also make the surface harder to finish. That is why loads are tested and adjusted to the target, not simply maximised.

Can I add air entrainer to bagged concrete?

Some bagged mixes are sold already air-entrained; most standard ones are not. Liquid air-entraining admixture can be added to the mix water at the manufacturer's dose, but without a mixer and an air meter you cannot confirm what you got. For a driveway, walk or patio in a freeze-thaw climate, air-entrained ready-mix tested at the truck is the reliable route.

How is air content tested on site?

With a pressure meter to ASTM C231 for normal-weight aggregate, or the volumetric 'roll-a-meter' to ASTM C173 for lightweight or porous aggregate. Both measure total air in a sample of fresh concrete taken from the middle of the load and take only a few minutes. Test the first truck and then regularly through the pour.

Can a sealer replace air entrainment?

No. A penetrating sealer slows water getting into the surface and helps any slab, but it cannot create the microscopic air voids that relieve freezing pressure inside the paste. Non-air-entrained flatwork in a severe freeze-thaw climate usually scales whatever is put on it.

When should you not use air-entrained concrete?

Leave it out in four cases: interior floors that get a hard steel-trowel or burnished finish, where it causes blisters and delamination; slabs inside heated buildings that never freeze; footings and walls that stay below the frost line; and any concrete in a climate where it never freezes while wet, such as Florida, the Gulf Coast or the low desert. In those cases the air only costs strength, about 5% per 1% of air.

Do I need air-entrained concrete in Texas, Florida or Arizona?

It depends on the weathering region on the building code map, not the state line. Florida, Houston, southern Louisiana and Phoenix are in the negligible zone, so the residential code does not require entrained air there. The Texas Panhandle, northern Arizona around Flagstaff and Reno, Nevada freeze hard enough that exterior concrete needs it. Ohio, Michigan and the rest of the northern states are severe: all exposed flatwork, steps and walls get 5–7% air.

Does a footing or foundation wall need air entrainment?

A footing below the frost line, covered by soil, does not: it never freezes while wet. Foundation walls, basement walls, retaining walls and pier tops that are exposed to weather do in moderate and severe climates; the US residential code asks for 3,000 psi air-entrained concrete for that vertical work. The buried footing under a retaining wall can be plain, the exposed stem should be air-entrained.

How do you add air entrainment to concrete?

With a liquid air-entraining admixture meeting ASTM C260, dispensed into the mix water at the ready-mix plant. Typical doses run from 1/4 to 4 fl oz per 100 lb of cement (16–260 mL per 100 kg); about 1 fl oz per 100 lb is a common starting point, which is roughly 45 fl oz for an 8 yd³ truck of a 564 lb/yd³ mix. The dose is then adjusted from air-meter readings, because temperature, slump, sand and fly ash all change how much air a given dose makes.

Does concrete need air to cure?

No. Concrete hardens by hydration, a reaction between cement and water, and it cures best when it is kept wet and sheltered from drying air; it even hardens underwater. Entrained air has nothing to do with curing. It is a durability feature that protects hardened concrete from freezing damage years later.

What is the difference between entrained and entrapped air?

Entrained air is deliberate: microscopic bubbles, mostly 0.0004 to 0.04 in (10 µm to 1 mm) across, spread evenly through the paste by an admixture. Entrapped air is accidental: larger irregular voids, 0.04 in (1 mm) and up, left by mixing and incomplete consolidation, usually 1–3% of the volume. Only entrained air protects against freeze-thaw. A pressure meter reads both together as total air.

Sources, author and reviewer

Air targets, exposure classes and mix limits come from ACI 318 as summarised by the NRMCA and from the ACI 211.1 proportioning tables; the mechanism, spacing factor and strength effect from the National Precast Concrete Association; finishing guidance from the American Society of Concrete Contractors.

  1. NRMCA, ACI 318 exposure categories and requirements (2017 Concrete in Focus). F0–F3 classes, maximum w/cm, minimum f′c, target air by aggregate size, SCM limits for F3
  2. Union College concrete course notes, ACI 211.1 air content and mixing water tables. recommended total air for mild, moderate and severe exposure by aggregate size
  3. National Precast Concrete Association, Air-Entraining Admixtures. 9% expansion of freezing water, 0.008 in spacing factor, about 5% strength loss per 1% air, ASTM C231 and C173, ASTM C260
  4. American Society of Concrete Contractors, Position Statement 1: Air-Entrained Concrete. entrained air not recommended for hard steel-troweled finishes (ACI 302.1R, ACI 301)
  5. City of Grand Rapids, MN, Concrete slabs handout (IRC Table R402.2). IRC minimum strengths by weathering region and 5–7% air for exposed concrete in moderate and severe weathering
  6. Master Builders Solutions, MasterAir AE 90 technical data sheet. ASTM C260 air-entraining admixture; trial dose range 1/4 to 4 fl oz/cwt (16–260 mL/100 kg); factors that change the dose
  7. Open Exam Prep, Air content, unit weight and yield. ±1.5% acceptance tolerance, pressure and volumetric test procedures
Rachel Sousa
Technical Writer & Content Lead · B.S. Civil Engineering, Purdue

Rachel holds a B.S. in Civil Engineering from Purdue University and spent 10+ years turning construction and engineering standards into clear documentation, including as documentation lead at a national ready-mix supplier. She writes every guide and calculator page on AllConcreteCalculator.com and owns the site’s editorial standards.

Published · Last updated · @rachelsousa101

Daniel Merritt, P.E.
Lead Structural Engineer · Licensed P.E., Civil/Structural · M.S. Structural Engineering, Texas A&M

Daniel is a licensed Professional Engineer with 18 years in concrete design and construction, from cast-in-place foundations and post-tensioned slabs to municipal bridge projects. He checks the engineering on this guide: that each code figure matches the provision it cites, the assumptions are stated, and the limits of the guidance are clear.

Technical review · @DanielMerrittco