Enter your slab span, thickness, concrete strength, and applied load to calculate maximum deflection and instantly check compliance with ACI 318 limits (L/360, L/480, L/240).
ACI 318 compliant
·
No sign-up required
·
Checks L/360, L/480, and L/240
·
Imperial & metric supported
✓ Simply-supported slab formula✓ Gross section Ie (conservative)✓ Three ACI 318 limits checked✓ Last verified October 2026
Written by Rachel Sousa· Reviewed by Daniel Merritt, P.E. — effective moment of inertia, long-term multiplier and deflection limits per ACI 318-19 (24.2.3, 24.2.4, Table 24.2.2); minimum thickness per Table 7.3.1.1, October 2026.
Enter Slab Parameters
Span of the one-way slab. For a cantilever, its length.Enter a span greater than 0, up to 60 ft.
Sets the deflection coefficient and the ACI 318 minimum thickness.
Overall depth, top to bottom.
Enter a thickness from 2 in to 4 ft.
Specified 28-day strength.
Enter 2,500 to 12,000 psi (17.2 to 82.7 MPa).
Unfactored service live load. ASCE 7: 40 psf residential, 50 psf offices, 100 psf assembly and corridors.
Enter a live load from 0 to 2,000 psf.
Finishes, partitions, ceilings. Self-weight (150 lb/ft³) is added automatically.Enter 0 to 2,000, or leave it blank.
Tension steel; sets the cracked moment of inertia.
On-center spacing of the bottom bars.Enter a spacing from 3 to 24 in.
ACI 318: ¾ in for slabs not exposed to weather or ground.Enter ½ to 4 in, leaving positive depth to the bars.
Live load that stays for long periods (storage, heavy furniture). Adds to creep.Enter 0 to 100%, or leave it blank.
Results appear instantly and update as you type. No sign-up required.
Deflection Results
Maximum Deflection
—
Deflection (inches)
—
Deflection (mm)
—
Span Ratio (L / δ)
ACI 318 Deflection Limit Checks
—
L/180 Limit
—
—
L/360 Limit
—
—
L/480 Limit
—
—
L/240 Limit
—
—Span (L)
—Thickness (h)
—Ec (psi)
—Ig (in⁴/ft)
—Effective Ie
—Live-Load Deflection
—Long-Term Addition
—Tension Steel
12 in strip. Dead load = 150 lb/ft³ × h + superimposed dead; w (lb/in) = psf ÷ 12
Ec = 57,000 √f'c; Ig = 12h³/12; fr = 7.5 √f'c; Mcr = fr·Ig ÷ (h/2)
Icr = b(kd)³/3 + n·As(d − kd)², n = 29,000,000 ÷ Ec, k = √(2ρn + (ρn)²) − ρn
Ie = Ig if Ma ≤ ⅔Mcr, else Icr ÷ [1 − (⅔Mcr/Ma)²(1 − Icr/Ig)] (ACI 318-19 Table 24.2.3.5)
δ = C·w·L⁴ ÷ (Ec·Ie): C = 5/384 simply supported, 1/185 one end continuous, 1/384 both ends, 1/8 cantilever
Live δ = δ(D+L) − δ(D); long-term = ξ ÷ (1 + 50ρ′) × δ(sustained), ρ′ = 0
Limits (Table 24.2.2): live ≤ L/180 flat roofs, L/360 floors; long-term + live ≤ L/480 (damage-sensitive) or L/240
How to Use This Concrete Slab Deflection Calculator
Identify your slab span and boundary conditions.
Enter the span and pick the support condition: simply supported, continuous at one or both ends, or cantilever. The calculator analyzes a one-foot strip of a one-way slab; for continuous spans it treats the continuous ends as fixed, which slightly underestimates deflection.
Enter the slab thickness (overall depth h).
Enter the overall thickness, concrete strength and the bottom bars. ACI 318 does not use the gross section once the slab has cracked: it uses an effective moment of inertia Ie between the gross and cracked values, which depends on the bars. The calculator works out both.
Enter concrete compressive strength and applied load.
Enter the unfactored live load and any superimposed dead load; self-weight is added. Separate loads matter because Table 24.2.2 checks live-load deflection against L/360 and the long-term-plus-live deflection against L/480 or L/240. Choose the duration for the long-term creep factor.
Read the compliance results and act on them.
Each limit card shows the deflection ACI 318 compares with it. Use L/360 for floors and L/180 for flat roofs that support nothing fragile; use L/480 where partitions, tile or glazing could be damaged, otherwise L/240. A failure means more thickness, more steel, a shorter span or continuity — and an engineer's review.
⚠ Pro Tip: The L/360 limit in ACI 318 Table 24.2.2 applies to live-load deflection only, not total deflection. If you run this calculator with the total load and compare to L/360, you will incorrectly flag compliant slabs as failures. Separate your live and total loads and use the right limit for each check.
Concrete Slab Deflection Formula
The calculator applies the elastic deflection formula for uniform load to a one-foot strip, with the stiffness ACI 318-19 prescribes: Ec = 57,000√f'c for normalweight concrete and the effective moment of inertia Ie, which falls from the gross value toward the cracked value as the moment exceeds the cracking moment. The example below is a simply supported slab that cracks under service load.
Step
Formula
Example (L = 14 ft, h = 8 in, f'c = 4,000 psi, 50 psf live, #4 @ 12 in)
Deflection of simply supported one-way slabs — 50 psf live load plus self-weight, #4 @ 12 in, ¾ in cover, effective Ie per ACI 318-19.
Span
Thickness
f'c (psi)
Live-Load Deflection (in)
L/360 Limit (in)
Status
10 ft
4 in
3,000
0.412
0.333
✗ FAIL
12 ft
5 in
3,000
0.522
0.400
✗ FAIL
15 ft
6 in
3,500
0.732
0.500
✗ FAIL
20 ft
6 in
3,000
1.884
0.667
✗ FAIL
20 ft
8 in
4,000
1.037
0.667
✗ FAIL
25 ft
8 in
4,000
2.217
0.833
✗ FAIL
30 ft
10 in
5,000
2.677
1.000
✗ FAIL
25 ft
6 in
3,000
4.359
0.833
✗ FAIL
30 ft
8 in
3,000
4.386
1.000
✗ FAIL
Values from the calculator, simply supported. Long spans with thin slabs crack under service load, which lowers Ie sharply — compare the 25 ft rows. Spans longer than about 20 times the thickness are under the ACI 318 minimum and need this calculation.
Which ACI 318 Deflection Limit Applies to Your Slab?
ACI 318 Table 24.2.2 sets maximum computed deflection limits based on the member type, the load considered, and what the slab is supporting below it. Using the wrong limit for your situation is the single most common mistake in deflection checking.
ACI 318-19 Table 24.2.2 — Maximum permissible calculated deflections.
Member Type
Condition
Load Considered
Limit
Flat roofs
Not supporting or attached to non-structural elements likely to be damaged by deflection
Live load only
L/180
Floors
Not supporting or attached to non-structural elements likely to be damaged by deflection
Live load only
L/360
Roofs or floors
Supporting or attached to non-structural elements likely to be damaged by deflection
Total load that occurs after attachment of non-structural elements
L/480
Roofs or floors
Supporting or attached to non-structural elements NOT likely to be damaged by deflection
Total load that occurs after attachment of non-structural elements
L/240
L/360 is the floor live-load limit, not a universal one, and it ignores creep. For floors and roofs carrying partitions, tile or other elements likely to be damaged, ACI 318 checks the deflection that occurs after they are attached — the long-term creep and shrinkage from sustained load plus the immediate live load — against L/480, or L/240 where damage is unlikely. The calculator runs all four checks.
5 Common Mistakes in Concrete Slab Deflection Checks
⚠️
Using total load against the L/360 limit.
L/360 in ACI 318 Table 24.2.2 applies to the immediate live-load deflection of floors. Comparing the total deflection with it over-sizes the slab. L/480 and L/240 are not total-load limits either: they apply to the long-term deflection from sustained load plus the immediate live load, after partitions or finishes are attached.
📐
Ignoring long-term (creep and shrinkage) deflection.
Creep and shrinkage keep deflecting a slab for years. ACI 318-19 multiplies the sustained-load deflection by λΔ = ξ ÷ (1 + 50ρ′), where ξ is 1.0 at 3 months, 1.2 at 6 months, 1.4 at 12 months and 2.0 at five years or more, and ρ′ is the compression steel ratio. With no top steel the long-term addition is twice the sustained deflection.
🔩
Using gross section Ig when the slab is cracked.
Gross Ig applies only while the slab is uncracked. ACI 318-19 uses Ie, which falls toward the cracked Icr once the service moment passes two-thirds of the cracking moment; for lightly reinforced slabs Icr can be a small fraction of Ig. The calculator reports whether the slab is cracked and the Ie used.
📏
Applying a one-way formula to a two-way slab.
This calculator solves a one-way slab strip. If your slab spans in two directions (aspect ratio shorter side to longer side > 0.5), two-way plate bending behavior kicks in and the actual deflection will be less than what a one-way strip analysis shows — but the calculation is far more involved. Applying the beam formula to a two-way slab is conservative, but using it to claim a two-way slab passes the limit when a one-way slab doesn't is incorrect.
📅
Checking deflection at the wrong load stage.
ACI 318 requires the deflection check to be performed under the load that occurs after the non-structural elements are attached — not at the time of pour, and not at ultimate load. Running the check under the total factored load (1.2D + 1.6L) instead of the unfactored service load produces a misleading result and has no basis in ACI 318 deflection provisions.
Frequently Asked Questions
ACI 318 Table 24.2.2 sets four limits depending on member type and loading condition. For floors not supporting damage-sensitive elements: L/360 for live load. For members supporting brittle partitions, cladding, or tile: L/480 for the incremental load occurring after attachment. For members supporting non-sensitive elements: L/240. For flat roofs not supporting sensitive elements: L/180. The most commonly cited limit — L/360 — applies to live load on typical floor slabs. Using the wrong limit for your situation leads to either over-design or a non-compliant slab.
It analyzes a one-foot strip with δ = C·w·L⁴ ÷ (Ec·Ie), where C depends on the supports (5/384 simply supported). Ec = 57,000√f'c, and Ie is the effective moment of inertia from ACI 318-19 Table 24.2.3.5 — equal to Ig while the slab is uncracked and falling toward the cracked Icr as the moment passes two-thirds of the cracking moment. Live-load and long-term deflections are separated as Table 24.2.2 requires.
Immediate deflection happens as load is applied. Long-term deflection comes from creep under sustained load and from shrinkage. ACI 318-19 (24.2.4) adds λΔ × the sustained-load deflection, with λΔ = ξ ÷ (1 + 50ρ′): ξ is 1.0 at 3 months, 1.2 at 6, 1.4 at 12 and 2.0 at five years or more, and ρ′ is the compression reinforcement ratio.
Because the moment of inertia (Ig) is proportional to the cube of the thickness (h³). Double the thickness and Ig increases by a factor of 8, cutting deflection to one-eighth. This is why going from a 6-inch slab to an 8-inch slab drastically reduces deflection. Span length has an even stronger effect — it appears to the fourth power (L⁴) in the deflection formula. A small increase in span can easily overwhelm the benefit of a thicker slab. In practice, the fastest way to control deflection is always to reduce the span first, then increase thickness second.
Yes, once the slab cracks. Before cracking, stiffness is set by the concrete (Ig). After cracking, more tension steel raises Icr and so Ie — the calculator shows the effect when you change the bars. Top (compression) steel reduces long-term deflection: with ρ′ = 0.5%, λΔ falls from 2.0 to 1.6; with 1%, to 1.33.
This calculator is specifically for one-way slab strips. For two-way slabs (aspect ratio of short span to long span greater than 0.5), plate bending distributes load in both directions and actual midspan deflection is significantly less than the one-way strip analysis predicts. Using this tool for a two-way slab gives a conservative result (over-predicts deflection), which is acceptable for preliminary screening. For accurate results on two-way slabs, use plate-theory methods or finite element analysis, or refer to the ACI 318 waffle slab and flat plate guidelines.
In order of typical effectiveness and cost: (1) Reduce the span — even a small reduction has a massive impact because deflection scales with L⁴. (2) Increase slab thickness — the most common fix, with deflection scaling with 1/h³. Going from 6 to 8 inches cuts deflection by more than half. (3) Increase concrete strength — f'c affects Ec, but only as a square root, so doubling f'c reduces deflection by just 29%. It's the least effective lever. (4) Use prestressed (post-tensioned) concrete — creates an upward camber that counteracts applied-load deflection. Common in parking structures and long-span commercial slabs. (5) Recheck the boundary conditions — a continuous slab has significantly less deflection than a simply-supported one. If the real slab is continuous, the simply-supported analysis you ran is over-conservative.
ACI 318-19 Table 7.3.1.1 gives the minimum thickness of one-way slabs not supporting or attached to partitions likely to be damaged by large deflections: span/20 simply supported, span/24 one end continuous, span/28 both ends continuous and span/10 for cantilevers, for normalweight concrete and Grade 60 bars (× (0.4 + fy/100,000) otherwise). Thinner slabs need calculated deflections — this calculator's check.
Stronger concrete has a higher modulus of elasticity (Ec), which means it deforms less under the same load. In the ACI formula, Ec = 57,000√f'c. Increasing f'c from 3,000 to 4,000 psi improves Ec by about 15%, reducing deflection by roughly 13%. From 3,000 to 5,000 psi gives a 29% improvement. This is a real but modest effect — it takes a 4x increase in f'c to cut deflection in half. In contrast, a 26% increase in slab thickness (say 6 to 7.5 inches) achieves the same reduction through the h³ relationship. Specifying higher-strength concrete is rarely the most efficient path to deflection control.
They're related but opposite concepts. Deflection is the downward displacement of a structural member under load. Camber is an intentional upward bow built into a member before loading, designed to offset anticipated deflection so that the member is approximately flat under the design load. Prestressed concrete slabs and precast members are often cambered. In cast-in-place concrete, camber is not typically used — deflection is controlled by choosing adequate thickness and span. The net deflection under service loads is what ACI 318 limits regulate.
A stiffness between the uncracked gross section Ig and the fully cracked section Icr. ACI 318-19 sets Ie = Ig while the service moment is at most two-thirds of the cracking moment, and Icr ÷ [1 − (⅔Mcr/Ma)²(1 − Icr/Ig)] above that.
The unfactored live load from the building code: ASCE 7 gives 40 psf for residential floors, 50 psf for offices and 100 psf for corridors and assembly areas, for example. Do not use factored loads in a deflection check.
Under ACI 318-19 Table 7.3.1.1 with Grade 60 bars: 8.4 in simply supported, 7.0 in with one end continuous and 6.0 in with both ends continuous. Thinner slabs can work if the calculated deflections meet Table 24.2.2.
Because L/480 includes creep. It compares the long-term deflection from sustained load — dead load plus any sustained live load, multiplied by up to 2.0 — plus the immediate live deflection, against a tighter limit. Heavy dead loads and thin slabs fail it first.
Worked Examples
Five slabs worked through. Enter the same inputs and the calculator will match.
Example 1: 14 ft simply supported, 8 in, 4,000 psi, 50 psf live, #4 @ 12
Cracked (Ie 236.5 in⁴/ft). Live 0.105 in (L/360 = 0.467 PASS); long-term + live 0.308 in against L/480 = 0.350 in.
Example 2: 20 ft simply supported, 6 in, 3,000 psi, 50 psf live, #4 @ 12
Cracked: Ie 35.7 in⁴/ft against Ig 216. Total immediate 4.042 in; live 1.884 in against 0.667 in. Below the l/20 = 12 in minimum.
Example 3: 20 ft both ends continuous, 8 in, 4,000 psi, 50 psf live
Coefficient 1/384. Live 0.020 in; long-term + live 0.098 in against L/480 = 0.500 in.
Example 4: 6 ft cantilever, 6 in, 4,000 psi, 50 psf live
Coefficient 1/8, moment wL²/2. Tip deflection 0.126 in; live 0.099 in against 0.200 in.
Example 5: Minimum thickness, 14 ft, both ends continuous, Grade 60
168 in ÷ 28 = 6.0 in (Table 7.3.1.1).
Calculator Assumptions, Sources and Limits
The calculator is a one-way strip check of service-load deflection. It is a design aid, not a design.
Values used by the calculator and where they come from.
Item
Value
Source or Basis
Stiffness
Ec = 57,000√f'c; Es = 29,000,000 psi; normalweight
ACI 318-19 19.2.2.1, 20.2.2.2
Cracking
fr = 7.5√f'c; Mcr = fr·Ig ÷ (h/2)
ACI 318-19 19.2.3.1, 24.2.3.5
Effective Ie
Ig if Ma ≤ ⅔Mcr, else Icr ÷ [1 − (⅔Mcr/Ma)²(1 − Icr/Ig)]
ACI 318-19 Table 24.2.3.5
Supports
Continuous ends modeled as fixed; Ie from the maximum positive (or cantilever) moment
B.S. Civil Engineering, Purdue University. 10+ years turning construction and engineering standards into clear, usable calculator documentation; former documentation lead at a national ready-mix supplier.
Licensed Professional Engineer (Civil/Structural), M.S. Structural Engineering, Texas A&M University. 18 years across commercial, municipal, and residential concrete. Reviews every structural calculator against ACI 318, ACI 332, and ASCE 7.